Fix and improve reactiveRangeCheckMode parameter documentation (#1049)
Browse files Browse the repository at this point in the history
Signed-off-by: Damien Jeandemange <[email protected]>
  • Loading branch information
jeandemanged authored Jun 24, 2024
1 parent 4845b1b commit 32960bd
Show file tree
Hide file tree
Showing 2 changed files with 19 additions and 9 deletions.
2 changes: 1 addition & 1 deletion docs/conf.py
Original file line number Diff line number Diff line change
Expand Up @@ -86,7 +86,7 @@
# List of patterns, relative to source directory, that match files and
# directories to ignore when looking for source files.
# This pattern also affects html_static_path and html_extra_path.
exclude_patterns = ['_build', 'Thumbs.db', '.DS_Store']
exclude_patterns = ['_build', 'Thumbs.db', '.DS_Store', 'README.md']

# Reference sections generation
autosectionlabel_prefix_document = True
Expand Down
26 changes: 18 additions & 8 deletions docs/loadflow/parameters.md
Original file line number Diff line number Diff line change
Expand Up @@ -31,7 +31,7 @@ The `lowImpedanceThreshold` property is an optional property that defines in per
(when $Z$ is less than the `lowImpedanceThreshold` per-unit threshold).
The default value is $10^{-8}$ and it must be greater than `0`.

**slackDistributionFailureBehavior**
**slackDistributionFailureBehavior**
This option defines the behavior in case the slack distribution fails. Available options are:
- `THROW` if you want an exception to be thrown in case of failure
- `FAIL` if you want the OuterLoopStatus to be `FAILED` in case of failure
Expand All @@ -58,7 +58,7 @@ When `readSlackBus` is set to true, `slackBusSelectionMode` is still used and se
- for e.g. synchronous components where no slack terminal extension is present.
- for e.g. synchronous components where more than `maxSlackBusCount` slack terminal extensions are present.

**mostMeshedSlackBusSelectorMaxNominalVoltagePercentile**
**mostMeshedSlackBusSelectorMaxNominalVoltagePercentile**
This option is used when `slackBusSelectionMode` is set to `MOST_MESHED`. It sets the maximum nominal voltage percentile.
The default value is `95` and it must be inside the interval [`0`, `100`].

Expand Down Expand Up @@ -137,7 +137,7 @@ When `useReactiveLimits` is set to `true`, this parameter is used to limit the n
is switching from PQ to PV type. After this number of PQ/PV type switch, the equipment will not change PV/PQ type anymore.
The default value is `3` and it must be greater or equal to `0`.

**phaseShifterControlMode**
**phaseShifterControlMode**
- `CONTINUOUS_WITH_DISCRETISATION`: phase shifter control is solved by the Newton-Raphson inner-loop.
- `INCREMENTAL`: phase shifter control is solved in the outer-loop

Expand All @@ -151,7 +151,7 @@ This parameter defines which kind of outer loops is used for transformer voltage

The default value is `WITH_GENERATOR_VOLTAGE_CONTROL`.

**transformerReactivePowerControl**
**transformerReactivePowerControl**
This parameter enables the reactive power control of transformer through a dedicated incremental reactive power control outer loop. The default value is `false`.

**incrementalTransformerRatioTapControlOuterLoopMaxTapShift**
Expand Down Expand Up @@ -257,10 +257,20 @@ and its solution status is flagged as failed.
The default values are `0.5` and `1.5` and they must be greater or equal to `0`.

**reactiveRangeCheckMode**
This parameter defines how to check the reactive limits $MinQ$ and $MaxQ$ of a generator. If the range is too small, the generator is discarded from voltage control.
- `MIN_MAX` mode checks if the reactive range at $MaxP$ is above a threshold and if the reactive range at $MinP$ is not zero.
- `MAX` mode if the reactive range at $MaxP$ is above a threshold.
- `TARGET_P` if the reactive range at $TargetP$ is above a threshold
OpenLoadFlow discards voltage control for generators with a too small reactive power range, because in practice a too
small reactive power ranger means limited to zero voltage control capability.

For a given active power output, the reactive power range is defined as $MaxQ - MinQ$ (always a positive value).
The *maximum* and *minimum* reactive range of a generator is:
- for generators without reactive limits: infinity
- for generators with reactive limits defined by a pair of [min/max values](inv:powsyblcore:*:*:#min-max-reactive-limits), both minimum and maximum reactive range are equal to $MaxQ - MinQ$
- for generators with reactive limits defined by a [reactive capability curve](inv:powsyblcore:*:*:#reactive-capability-curve), the minimum (resp. maximum) reactive range is obtained by finding the curve point having the minimum (resp. maximum) $MaxQ - MinQ$.

The `reactiveRangeCheckMode` parameter defines how generator reactive power range is to be tested. If the test does not pass,
meaning the reactive power range is too small, then the voltage control is disabled:
- `MIN_MAX` mode tests if the minimum reactive range is not `0 MVAr` and if the maximum reactive range is above `1 MVAr`.
- `MAX` mode tests if the maximum reactive range is above `1 MVAr`.
- `TARGET_P` tests if the reactive range at $TargetP$ is above `1 MVAr`.

The default value is `MAX`.

Expand Down