-
Notifications
You must be signed in to change notification settings - Fork 23
FAQ & Troubleshooting
Try changing the "Master Member ID", this is most likely the problem. If you don't know which identifier is valid for your boiler, you need to use brute force.
Receiving a SUCCESS
response to ID 1
in the logs indicates that the master member ID is probably correct.
Try on "Opentherm summer/winter mode", "Opentherm CH2 enabled", "Opentherm heating CH1 to CH2" checkboxes one by one and all together on the "setup" page. If this doesn't work, see above.
Some boilers require the target temperature on the panel to be set to at least the maximum expected to be set by OpenTherm, acting as a hard limit on the OpenTherm requests. Some boilers report the target temperature on the panel as the max heating limit in OpenTherm diagnostic.
The heating must be enabled before the controller will issue a target temperature request to the boiler.
Uncheck "Opentherm DHW present" on the "setup" page.
Try on "Modulation sync with heating" checkbox on the "setup" page.
Try off "Modulation sync with heating" checkbox on the "setup" page
You need to open the device page, at the very bottom of the Configuration/Diagnostic card you will see the inscription “+N entities not shown”, click on it, a list of deactivated entities will appear. Select the one you want to activate and click on it. In the window that appears at the top there will be a gear icon (settings), click on it. In the window that appears, turn on the "Enabled" option and save. After some time, the activated entity will appear in the list.
This is normal; when connecting OpenTherm devices, the setpoint temperature is usually not displayed and does not change on the boiler display.
(ID_1_request & 0xFFFF) / 256d
= requested target temperature in °C
You can turn on an external pump by the event of turning on the binary_sensor.opentherm_heating sensor in the home assistant.