forked from mbs38/spicierModbus2mqtt
-
Notifications
You must be signed in to change notification settings - Fork 0
/
example.csv
We can make this file beautiful and searchable if this error is corrected: It looks like row 2 should actually have 7 columns, instead of 1 in line 1.
78 lines (74 loc) · 3.02 KB
/
example.csv
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
"type","topic","col2","col3","col4","col5","col6"
# DO NOT REMOVE THE FIRST LINE!
# Example register definition file.
#
# You need to define a Poller and then one or more References for that poller.
# The Poller will 'poll' the slaveid and bring back 1 or more registers/bits.
# The References must then match up with the polled range to define the topic for each.
#################################################################################
# Poller-object
# Columns:
# type, topic, slaveid, reference, size, functioncode, rate
#
# Possible values for columns:
# type: poll
# topic: any string without spaces
# slaveid: integer 1 to 254
# reference: integer 0 to 65535 (Modbus references are as transmitted on the wire.
# In the traditional numbering scheme these would have been called offsets. E. g. to
# read 400020 you would use reference 20.)
# size: integer 0 to 65535 (No. of registers to poll, value must not exceed the limits of Modbus of course)
# functionscode: coil, input_status, holding_register, input_register
# rate: float 0.0 to some really big number
#
# functionscode equivalents: coil, input_status, holding_register, input_register
# 1 2 3 4
#
# Example poller-object:
# poll,someTopic,1,2,5,coil,1.0
# Will poll states of 5 coils from slave device 1 once a second, starting at coil 2.
#
#################################################################################
# Reference-Object
# Columns:
# type, topic, reference, rw, data type
# type: ref
# topic: any string without spaces
# reference: integer 0 to 65535 (This is the modbus offset and should match the poller ref)
# rw: r, w or rw
# data type (registers only): uint16, float32BE, float32LE, uint32BE, uint32LE, string (defaults to uint16)
#
# Example reference-object:
# ref,light0,2,rw
# The state of coil 2 will be published to mqtt with the topic modbus/someTopic/state/light0
# if column 3 contains an 'r'.
# If you publish a value (in case of a coil: True or False) to modbus/someTopic/set/light0 and
# column 3 contains a 'w', the new state will be written to the slave device.
#
#################################################################################
# Columns:
# type, topic, slaveid, reference, size, functioncode, rate
# type, topic, reference, rw, data type,
#
poll,kitchen,7,0,4,coil,0.002
ref,light0,0,rw
ref,light1,1,rw
ref,light2,2,rw
ref,light3,3,rw
poll,kitchen,7,0,12,holding_register,0.5
ref,someWritableRegister,0,rw
poll,heating,32,52,4,holding_register,1
ref,temperature_pre,52,r
ref,temperature_post,53,r
ref,temperature_setpoint,54,rw
ref,temperature_outdoors,55,r
poll,ioModule,10,1,2,input_status,0
ref,doorbell,1,r
ref,mailbox_sensor,2,r
poll,garage,1,0,10,holding_register,2
ref,counter1,0,rw,float32BE
#register 0 as low word, register 1 as high word
ref,counter2,1,rw,uint16
#treat the contents of register 1 as unsigned int. (note that counter1 overlaps counter2. This is possible and may be useful)
ref,somestring,3,rw,string6
#registers 3, 4 and 5 as a 6 character string